General
This environmental structure known as a Relocatable,
Environmentally Controlled Enclosure is designed and constructed to meet the specific needs of the communication
industry. The units are constructed in 8' to 16' widths incremental at 8" with an internal ceiling height of
(9' 3"). The length will be 8' to 40' incremental at 8". Buildings to meet Uniform building code B4, Occupancy,
BOCA National Building Code Type 4A and UL ISO, CSA and UL Standards.
A Service Manual will be provided
with each building in a wall mounted holder. The manual will outline Maintenance and Repair information for
all equipment used in the building and the building itself, with contact names and phone numbers for assistance
and replacement, for both warranty and after warranty service.
Structural Specifications
The frame assembly is fabricated
from structural steel main members and steel cross members. The frame is primed with a rust inhibitor primer
and finish coated with 2 coats of a high quality enamel.
Floor
The floor assembly consists of a sub-floor of 30 Ga.
galvanized steel. The floor underlayment is 3 layers, one of 3/4" exterior grade, plugged and a touch sanded
plywood attached to the floor joist and a top layer flooring of 1/4" exterior grade plywood, positioned such
that all seams are staggered, and assembled with screws. The floor covering is 1/8" X 12" X 12" commercial
grade vinyl tile. Floor insulation is R-20 Fiberglass with vapor barrier.
Walls
Exterior walls are 24 gauge Butler Steelox flat panels
formed from zinc coated steel with factory applied color and a smooth surface. Standard wall finish is 1/2"
beige vinyl wall board panels with brown divider strips. R-12 insulation plus 6 mil. vapor barrier. The walls
are bolted directly to the frame around the perimeter of the floor assembly and employ 14 Ga. galvanized shear
plate, bolted to the wall assembly and the frame.
Roof
Exterior roofing is Butler Steelox 18 GA panels, roll
formed from zinc coated steel with optional factory applied color coating and a smooth surface. (Galvalum 18 gauge)
with 8" overhang. 6 MIL Polyethylene film will be used to line all interior walls and floor under paneling.
Interior ceiling are Butler Steelox panels, roll formed as above with an embossed finish (Antique White, 24 gauge).
Door
(1) 36" X 80" insulated steel door finished in Antique
White. The door jamb is a welded steel frame with vinyl seal. Doors are set in a door frame structure integral
with the wall assembly. Door closer, 603PAL, Door lock, Unican lock on door.
Electrical
Electrical distribution is:
200 Amp system,
single phase 60 Hz 220 volt panel with forty two (42) circuits. Transfer switch and emergency generator
receptacle are optional. All wiring conforms to National Electric Code. Individual circuits with high quality
circuit breakers are provided in the distribution panels. 110 volt outlets are located on each wall. Dual
bulb, low profile 40 watt, 110 volt 60 Hz florescent lights are provided on the ceiling, complete with bulb
guards. Exterior light shall be a 100 watt Vandal proof light.
- Safety Equipment and Alarms
The smoke detector has
photoelectric sensing equipment, for local and remote alarms. An alarm terminal block shall be provided capable
of monitoring and reporting the following:
Door openPresence of smokeHigh or low temperature
All alarms are to be provided as a normally open dry circuit closed to alarm. Customers will be responsible
for integrating the alarm package into switching equipment scan points.
Cable Tray
12" wide X 4" deep aluminum.
- Mechanical
Air Conditioning is optional in the following
configurations:Packaged units.Split systems.Wall mounts.
Fire Suppression System
FM 200 and components.
Warranty
Original Equipment Manufacturers (OEM) warranties
are forwarded to the customer. The enclosure manufacturers warrants the enclosure to be free of defects and
workmanship for a period of not less than 1 full year.